All fire resisting glazed systems were fully tested by Warrington Fire Research Centre.

Full copies of the fire test reports are available on request from Henshaw Technical Sales Department. We confirm that many other project tests and fire assessments are also available to cover the full range of performance requirements.

Report No. System / Glass Type Integrity (min) Insulation (min)
50438 S60 Pyroscreen Pyran 62 not tested
50439 A60 Pyroscreen/Pyran 68 68
50440 S60 Pyrodoor Pyran 77 not tested
50504 A90 Pyroscreen/Pyrostop 117 111
52912 AX60 Pyroscreen (external system) 75 64
54279 H1201Pyroscreen/Pyrostop 113 152
59605 A90 Pyroscreen/Contraflam 89 89
61062 A30 Pyroscreen/Pyrostop 66 47
65549 S30 Pyroscreen/Tempaflam 44 not tested
107441 Pyroscreen/Clearview (all glass) 63 63
114639 Pyroscreen 50 (slimline) 75 65